| Sign In | Join Free | My benadorassociates.com |
|
| Categories | Industrial Automation Products |
|---|---|
| Model Number: | 6GK7443-5DX04-0XE0 |
| Certification: | UL CE |
| Place of Origin: | Germany |
| MOQ: | 1 PCS |
| Price: | consult for best discount |
| Payment Terms: | T/T, , Western Union,Paypal,, MoneyGram,, L/C |
| Supply Ability: | 50 pcs per month |
| Delivery Time: | 2-5 days |
| Packaging Details: | original package |
| Application: | Industrial Communication |
| Production Range: | S7-400 Communication CP443-5 Extended |
| Fuction: | Extended for connection of SIMATIC S7-400 to PROFIBUS DP |
| Type of supply voltage: | DC |
| Condition: | New and original |
| Warranty: | 12 Months |
| Company Info. |
| Yueqing Richuang Automation Equipment Co.,Ltd |
| Verified Supplier |
| View Contact Details |
| Product List |
6GK7443-5DX05-0XE0 Communications Processor CP 443 Of S7-400 Industrial Automation Products
Overview

Application
The CP 443-5 Extended is the communications processor of the SIMATIC S7-400 for the PROFIBUS bus system.
It relieves the CPU of communication tasks and supports additional connections.
Communication possibilities of the S7-400 using communication modules:
The number of CPs that can be used is dependent on the performance range of the CPU and on the communications services used.
Function
The CP 443-5 Extended provides access to different communication services of the PROFIBUS bus system:
| Product type designation | CP 443-5 Extended | |
| Communications processor CP 443-5 Extended for connection of SIMATIC S7-400 to PROFIBUS DP, S5-compatible, PG/OP and S7 communication | ||
| Transmission rate | ||
| Transfer rate | ||
| ● at the 1st interface / acc. to PROFIBUS | 9.6 kbit/s ... 12 Mbit/s | |
| Interfaces | ||
| Number of interfaces / acc. to Industrial Ethernet | 0 | |
| Number of electrical connections | ||
| ● at the 1st interface / acc. to PROFIBUS | 1 | |
| Type of electrical connection | ||
| ● at the 1st interface / acc. to PROFIBUS | 9-pin Sub-D socket (RS485) | |
| Supply voltage, current consumption, power loss | ||
| Type of voltage / of the supply voltage | DC | |
| Supply voltage / 1 / from backplane bus | 5 V | |
| Supply voltage | 5 V | |
| Relative symmetrical tolerance / at DC | ||
| ● at 5 V | 5 % | |
| Consumed current | ||
| ● from backplane bus / at DC / at 5 V / typical | 1 A | |
| Power loss [W] | 5 W | |
| Permitted ambient conditions | ||
| Ambient temperature | ||
| ● during operation | 0 ... 60 °C | |
| ● during storage | -40 ... +70 °C | |
| ● during transport | -40 ... +70 °C | |
| Relative humidity / at 25 °C / without condensation / during operation / maximum | 95 % | |
| Protection class IP | IP20 | |
| Design, dimensions and weight | ||
| Module format | Compact module S7-400 single width | |
| Width | 25 mm | |
| Height | 290 mm | |
| Depth | 210 mm | |
| Net weight | 0.65 kg | |
| Product properties, functions, components / general | ||
| Number of units | ||
| ● per CPU / maximum | 14 | |
| ● Note | The number of CPs that can be operated as DP masters depends on the number of CP 443-1 Advanced processors operating in the S7-400 station as PROFINET IO controllers. Up to 10 CPs can be operated in total: up to 4 as PROFINET IO controllers (CP 443-1 Advanced); up to 10 as DP masters (CP 443-5 Extended) | |
| Performance data / open communication | ||
| Number of possible connections / for open communication / by means of SEND/RECEIVE blocks / maximum | 32 | |
| Amount of data | ||
| ● as user data per connection / for open communication / by means of SEND/RECEIVE blocks / maximum | 240 byte | |
| Performance data / PROFIBUS DP | ||
| Service / as DP master | ||
| ● DPV1 | Yes | |
| Number of DP slaves / on DP master / usable | 125 | |
| Amount of data | ||
| ● of the address area of the inputs / as DP master / total | 4096 byte | |
| ● of the address area of the outputs / as DP master / total | 4096 byte | |
| ● of the address area of the inputs / per DP slave | 244 byte | |
| ● of the address area of the outputs / per DP slave | 244 byte | |
| Performance data / S7 communication | ||
| Number of possible connections / for S7 communication | ||
| ● maximum | 48 | |
| Performance data / multi-protocol mode | ||
| Number of active connections / with multi-protocol mode | ||
| ● without DP / maximum | 59 | |
| ● with DP / maximum | 54 | |
| Configuration software | ||
| ● required | STEP 7 V5.4 SP4 or higher and NCM S7 for PROFIBUS | |

|