| Sign In | Join Free | My benadorassociates.com | 
              
  | 
      
| Categories | Modicon Quantum PLC | 
|---|---|
| Brand Name: | Schneider | 
| Model Number: | 140DDO35301 | 
| Certification: | CE | 
| Place of Origin: | France | 
| MOQ: | 1 PC | 
| Price: | 1-500USD | 
| Payment Terms: | T/T, Western Union | 
| Supply Ability: | 30 PCS/ PER Month | 
| Delivery Time: | 2-3 days | 
| Packaging Details: | original box | 
| Brand: | Schneider | 
| Model: | 140DDO35301 | 
| range of product: | Modicon Quantum automation platform | 
| Origin Of Country: | France | 
| addressing requirement: | 2 output words | 
| discrete output voltage: | 24 V DC | 
| Company Info. | 
| Shenzhen Viyork Technology Co., LTD | 
| Verified Supplier | 
| View Contact Details | 
| Product List | 
Schneider Automation Telemecanique Modicon Quantum DDO, DDO 353
01,140DDO35301
Quick Details:
SCHNEIDER ELECTRIC
MODICON
140-DDO-353-01
140DDO35301
OUTPUT MODULE
DC OUT 24VDC
4X8 SOURCE
One Year warrabty
SPECIFICATION
Manufacturer  | Schneider Electric  | 
Series  | Modicon Quantum  | 
Module format  | Standard  | 
Product or component type  | Dc discrete output module  | 
Discrete output number  | 32  | 
Group of channels  | 4 groups of 8  | 
Discrete output logic  | Positive logic (source)  | 
Addressing requirement  | 2 output words  | 
Discrete output voltage  | 24 V DC  | 
Output voltage limits  | 19.2...30 V  | 
Absolute maximum output  | 50 V for 1 s decaying pulse  | 
Voltage drop  | 0.4 V 0.5 A  | 
Maximum load current  | 16 A per module  | 
16 A per module  | |
4 A per group  | |
4 A per group  | |
Surge current  | <= 2 A  | 
<= 2 A  | |
Response time  | <= 0.1 ms at state 1 to state 0  | 
<= 1 ms at state 0 to state 1  | |
Leakage current  | <= 1 mA 24 V  | 
Load inductance  | Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))  | 
Inductance(H) = 0.5/((current(A))² x (switching frequency(Hz)))  | |
Fault indication  | Loss of field power  | 
Blown fuse  | |
Associated fuse rating  | 3 A each point  | 
3 A each point  | |
5 A per group  | |
5 A per group  | |
Isolation between channels and bus  | 1780 Vrms DC for 1 minute  | 
Isolation between group  | 500 Vrms DC for 1 minute  | 
Protection type  | Internal output protection by 5 A fuse per group  | 
Power dissipation  | 5 W  | 
Marking  | CE  | 
Local signalling  | 1 LED green bus communication is present (Active)  | 
1 LED red external fault detected (F)  | |
32 LEDs green input status  | |
Bus current requirement  | <= 330 mA  | 
<= 330 mA  | 
| 
                                 |