Sign In | Join Free | My benadorassociates.com
benadorassociates.com
Products
Search by Category
Home >

SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment

Categories Gas Insulated Switchgear
Brand Name: Knkong
Model Number: SF6 GIS HXGN-40.5
Certification: IEC ISO GB
Place of Origin: China
MOQ: 1
Payment Terms: L/C, T/T
Supply Ability: 100 Unit per month
Delivery Time: 30 days
Packaging Details: Standard export packaging
Using Voltage: 36KV
Using Current: 1250A
Using Frequency: 50/60Hz
Original: China
OEM/ODM: Available
Type: Fully insulated
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment

SF6 metal-clad gas-insulated switchgear 36KV MV GIS electrical equipment

Voltage: 36KV

Current: 1250A

Type: Metal-clad SF6 fully insulated


General

The F-unit unit is a fuse switch unit, which is a two-position load switch.
The equipment unit and load switch farm load switch fuse combination.
The grounding switch adopts a dual-mode and grounding on both sides of the fuse at the same time, so as to ensure that the fuse is not charged at the same time except that the grounding switch is closed. The double grounding switch adopts a mechanical interlock, and the primary grounding operates the grounding of the two grounding switches at the same time.

Technical Data

No.ItemUnitParameter
1Rated voltagekV122436
2Rated frequencyHz50/60
3Rated currentA630(1250*)
4

1min Power frequency

withstand voltage

wetkV385070
drykV486085
5Lightning impulse withstand voltagekV75125/150170
6Rated short circuit breaking current (peak)kA806363
7Rated active load and close circuit breaking currentA635050
8Rated transferring currentA170012001200
9Rated short circuit making a current (peak)kA806363
10Rated cable(line) charging breaking currentA

50 and 10

50/10

11Cable charge breaking current in earthing faultA202020
12Rated withstand current (peak)kA806363
13Short-time withstand current (2s)kA252020
14Mechanism lifetimes500020002000

Buy SF6 Metal Clad Gas Insulated Switchgear 36KV MV GIS Electrical Equipment at wholesale prices
Send your message to this supplier
 
*From:
*To: Knkong Electric Co.,Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0