Sign In | Join Free | My benadorassociates.com
benadorassociates.com
Products
Search by Category
Home > Used Tools >

Single Zone FM200 Gas Suppression System Fm200 Automatic Fire Extinguisher

Categories FM200 Fire Suppression System
Brand Name: Rongxiao
Model Number: QMQ4.2/180W QMQ4.2/150W QMQ4.2/120W QMQ4.2/90W QMQ5.6/180W QMQ5.6/150W QMQ5.6/120W QMQ5.6/90W QMQ5.6/70W
Certification: CAL,CMA,CNAS,,CCC
Place of Origin: Guangzhou City, Guangdong Province, China
MOQ: 1 set
Price: Negotiation
Payment Terms: L/C, D/P, Western Union, T/T, Credit card
Supply Ability: 18000 sets per week
Delivery Time: 10 days, subject to quantity negotiation
Packaging Details: Plywood outer box with bubble bag or paper
Working Power: DC 24V 1.5A
Activation Method: Automatic or Manual
Standard Of Examination: GB25972-2010
Detection System: Heat & Smoke Detectors
Storage Temperature: -10°C to 50°C
Usage: Gas Fire Extinguishing
Application: Protecting critical assets and sensitive equipment
Discharge Time: 10 seconds or less
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Single Zone FM200 Gas Suppression System Fm200 Automatic Fire Extinguisher


1. Equipment technical performance parameters:

Temperature℃Pressure Mpa(20℃)Power Supply
design temperatureusage temperatureFire extinguishing agent bottle groupNitrogen-driven bottle group

Main electricity


Standby power


0-500-500.313.5

AC

220V

DC24V

2. bottle group specifications and storage pressure

Bottle group nameModel specification (l)Storage pressure (20℃)
Nitrogen start-up bottle group86Mpa
Nitrogen automatic bottle group7013.5Mpa
Fire extinguishing agent bottle group70901201501800.3Mpa

3. Startup method

The pipe network type HFC-227ea fire extinguishing system has three startup methods, namely automatic startup, electrical manual and mechanical emergency manual.

(I) Automatic startup state

The gas fire extinguishing alarm controller is generally equipped with two different types of fire detectors. The control host has "automatic" and "manual" conversion functions (the conversion switch can also be set separately outside the protection zone). When it is placed in the "automatic" position, the fire extinguishing system is in automatic state.

When only one detector sends a fire signal, the control host starts the indoor sound and light alarm to notify the fire, but does not start the fire extinguishing device.

When two detectors send a fire signal, the control host starts the indoor and outdoor sound and light alarms, closes the opening of the protection zone, and enters the fire extinguishing startup delay. After the set delay time is reached, the fire extinguishing device is automatically started, a fire extinguishing command is issued, and the solenoid valve is opened to release the gas cylinder gas. The gas cylinder gas opens the fire extinguishing agent container valve through the startup pipeline to release the fire extinguishing agent and implement fire extinguishing.

If it is found that the fire extinguishing device does not need to be started during the spraying delay process, the "Emergency Stop" button outside the protection area or on the controller can be pressed to terminate the fire extinguishing command, which is valid within the set delay time.

The automatic start delay time of the system can be continuously adjusted within the range of 0~30s. When the adjustable level is divided into levels, the interval of each level should not be greater than 10s, and the delay time setting error should not be greater than 20% of the set time.


Company introduction:

Guangzhou Rongan Fire Protection Equipment Co., Ltd. is a professional manufacturer of fire protection facilities integrating R&D, production, design and sales services. The company has experts from the national fire protection industry standards committee and a group of professional technical service teams with more than ten years of experience in the fire protection industry, and will spare no effort to provide you with the most intimate and professional comprehensive technical solutions for fire protection engineering products. "Rongxiao" series products produced by the company have passed the national compulsory product certification and the national fixed fire extinguishing system inspection center, with reliable quality and stable performance, and the factory has passed the ISO9001 quality system certification.


Frequently asked questions:

Q1: Are you a manufacturer or a trading company? A1: We are manufacturers.

Q2: How long is the delivery time? A2:10 days, which can be negotiated according to the quantity.

Q3: How to deal with the fault? A3: During the warranty period, we will provide you with a remote emergency plan during working hours. During the free maintenance period, the company will replace spare parts or complete machines that have failed due to defects or quality problems free of charge.


Buy Single Zone FM200 Gas Suppression System Fm200 Automatic Fire Extinguisher at wholesale prices
Send your message to this supplier
 
*From:
*To: Guangzhou rongan fire equipment co. LTD
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0