Sign In | Join Free | My benadorassociates.com |
|
Categories | Heat Release Rate Tester |
---|---|
Brand Name: | GOLD |
Model Number: | GD-ISO 1716 |
Certification: | ISO |
Place of Origin: | China |
MOQ: | 1set |
Price: | Negotiation |
Payment Terms: | L/C, D/A, D/P, T/T, Western Union, MoneyGram |
Supply Ability: | 5sets/Month |
Delivery Time: | 30days |
Packaging Details: | Standard Wooden Case |
Name: | Building Materials Bomb Calorimeter |
Standard: | ISO 1716 |
Power: | AC220V±10% 50Hz |
Timer: | accuracy of 0.5s |
Bomb capacity: | (300 ± 50) mL |
wall thickness: | 1mm |
Ambient temperature: | (10 ~ 35) ℃, humidity ≤80% |
Heat repeatability error: | ≤0.2% |
Company Info. |
Chongqing gold mechnical and electrical equipment Co., Ltd |
Verified Supplier |
View Contact Details |
Product List |
Building Materials Heat Release ISO 1716 Bomb Calorimeter Testing Apparatus
ISO1716 Bomb Calorimeter Product Introduction:
This instrument is specially used to determine the combustion calorific value of building materials. It can accurately measure the total calorific value (high calorific value) and net calorific value (low calorific value) of combustion, which fully complies with the requirements of GB/T 14402-2007 "Determination of Combustion Calorific Value of Building Materials" and ISO 1716:2002 "Fire Reaction Test of Building Products-Determination of Combustion Calorific Value" international standards.
It adopts high-precision constant temperature oxygen bomb
technology to ensure the stability and reliability of the test
process. It is suitable for the calorific value analysis of various
building materials, fireproof products and other solid
combustibles, and provides accurate data support for product
quality control, fireproof performance evaluation and scientific
research experiments.
The microcomputer automatic calorimeter is mainly suitable for measuring the calorific value of coal, petroleum, chemical industry, food, wood, explosive and other solid or liquid combustible substances in electric power, coal, paper making, cement, agriculture and animal husbandry, scientific research, teaching and other industries or departments.
ISO1716 Bomb Calorimeter Standards:
• GB/T 14402-2007
• ISO1716-2002
ISO1716 Bomb Calorimeter Technical Specification:
Calorimetric bomb capacity | (300±50)ml |
Calorimetric elastic pressure | 21Mpa |
crucible | 25mm |
high | (14-19)mm |
wall thickness | 1mm |
timer | 0.5s |
voltage | AC220V±10%50Hz |
maximum power usage | 0.5KW |
ambient temperature | (10~30)℃ |
ISO1716 Bomb Calorimeter Features:
1. Capacity: (300±50)mL
2. Mass: 3.25 kg
3. The thickness of the barrel is greater than 1/10 of the inner
diameter of the barrel
4 .The lid can accommodate the crucible and the electronic ignition
device. The lid and all sealing devices can withstand an internal
pressure of 21Mpa
5 .The inner wall of the barrel is made of USU304# stainless steel,
which can withstand the erosion of the sample combustion products
and resist the pitting corrosion and intergranular corrosion caused
by the acidic substances produced by the combustion.
Calorimeter:
1. The outer cylinder of the calorimeter is a double-layer
container with an insulating cover. The inner and outer walls are
filled with insulating materials. The outer cylinder is filled with
water. There is a 10mm gap around the outer wall and the inner wall
of the calorimeter. The bomb is supported by three points with the
smallest contact area.
2. The inner cylinder of the calorimeter: It is a polished metal
container used to hold the oxygen bomb, which can completely
immerse the oxygen bomb in water. The inner cylinder has an
automatic water filling device. If the test water is insufficient,
the equipment will automatically replenish it. The volume is
2200ml.
3. Agitator: Driven by a constant speed motor to avoid heat
transfer of the calorimeter. The parts where the stirring shaft
contacts the outer barrel cover and the outer barrel quality
inspection are separated by an insulating gasket. A magnetic
stirring device with the same performance is selected; stirring
power: 3W; stirring speed inner cylinder: 375r/min.
4. Temperature measurement device: temperature resolution: 0.0001℃,
using the American OMEGA high-precision PT100 sensor. Temperature
measurement: temperature derivative of platinum resistance 1/1000;
5. Crucible: Made of stainless steel, two pieces are delivered.
6. Timer: Record test time, accurate to S, accuracy is 0.1s/h
7. Power supply: AC 185~245V.
8. Pressure gauge and needle valve: Installed on the oxygen supply
circuit, display the pressure of the oxygen bomb during
oxygenation, accurate to 0.1Mpa, oxygen bomb oxygenation pressure
0~3.5Mpa without leakage.
Packing & Delivery:
Packing Details :Plywood case for ISO 1716 Bomb Calorimeter
![]() |