| Sign In | Join Free | My benadorassociates.com |
|
| Categories | Cummins Diesel Generator |
|---|---|
| Place of Origin: | Sichuan, China |
| Brand Name: | JIWEI |
| Model Number: | 4B3.9-G1 |
| Price: | Negotiabce |
| Certification: | CE |
| MOQ: | 1 |
| Payment Terms: | T/T |
| Rated Voltage: | 220V, 380V |
| Rated Current: | 36A-39.6A |
| Speed: | 1800RPM, 1500RPM |
| Frequency: | 50/60hz |
| Starting system: | 12V DC Electric Start, 24V DC Electric Start |
| Type: | Container Type, Open Frame, Mobile Type, Silent type |
| Cooling System Type: | Water Cooling System |
| Warranty: | Other |
| Rated power: | 20KW 22KW 25KVA 28KVA |
| Engine: | 4B3.9-G1 |
| Product name: | 20KW 22KW 25KVA 28KVA Cummins diesel generator set |
| Color: | customizable |
| Company Info. |
| Sichuan Jiweicheng Electric Power Equipment Co., Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |
overview
Characteristic advantage
● High reliability: After strict quality control and production process, it can operate stably even in harsh environments and provide reliable power protection.
● Good fuel economy: Using advanced combustion technology and turbocharging technology, low fuel consumption rate and high energy efficiency.
● Low emission: The use of low emission technology, effectively reduce exhaust gas emissions, reduce environmental pollution.
Low noise: The use of noise control technology, noise level in line with national standards, to create a good environment for users.
Application field
● Industrial field: Suitable for petrochemical, iron and steel smelting, pharmaceutical, food processing and other industries with high requirements for power stability.
● Construction field: can be used in construction sites, commercial centers, hospitals and other places to ensure the stability of power supply.
● Other fields: It can also be used as a backup power supply in energy fields such as wind power generation and solar power generation, as well as data centers, communication base stations and other places.
GENERATINGSETDATA | |
Relatedrange of voltage setting | ≥±5% |
Steady-state voltage deviation | ≤±1% |
Transientvoltagedeviation(100 % suddenpower decrease) | ≤+25% |
Transient voltage deviation(suddenpowerincrease) | ≤-20% |
Voltagerecoverytime (100% suddenpowerdecrease) | ≤6S |
Voltagerecovery time (suddenpowerincrease) | ≤6S |
Relatedrange of frequency setting | 0-5% adjustable |
Steady-state frequencyband | ≤1.5% |
Transientfrequencydeviation(100 % suddenpower decrease) | ≤+12% |
Transient frequency deviation(suddenpowerincrease) | ≤-10% |
Frequencyrecoverytime(100 % suddenpower decrease) | ≤5S |
Frequencyrecovery time (suddenpowerincrease) | ≤5S |





|