| Sign In | Join Free | My benadorassociates.com |
|
| Categories | Custom Power Distribution Box |
|---|---|
| Productname: | Custom Distribution Cabinet Assembly |
| Place of Origin: | XiaMem,China |
| MOQ: | 100 |
| Payment Terms: | TT |
| Lockingmechanism: | Key lock / Handle lock / Electronic lock |
| Cableentry: | Bottom entry / Top entry / Side entry |
| Protectionlevel: | IP54 / IP65 / IP66 |
| Ventilation: | Natural ventilation / Forced ventilation / None |
| Operatingtemperaturerange: | -40°C to +60°C |
| Price: | negotiable |
| Mountingtype: | Wall-mounted / Floor-standing / Pole-mounted |
| Material: | Steel / Aluminum / Stainless Steel |
| Company Info. |
| Xiamen Rongmai Electrical Equipment Co., Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |
The Compact Modular Custom Distribution Cabinet Assembly is engineered to meet the high-density power requirements of modern commercial complexes and shopping malls. Designed for spatial efficiency, continuous operation, and seamless load scalability, this low-voltage power distribution solution ensures uninterrupted electricity supply across diverse retail zones, food courts, and anchor stores.
To ensure reliable performance under fluctuating commercial electrical loads, every custom distribution cabinet assembly is manufactured in compliance with international low-voltage switchgear standards.
| Technical Parameter | Specification Standard |
|---|---|
| Rated Operational Voltage (Uₑ) | 400V AC / 690V AC (50/60 Hz) |
| Rated Insulation Voltage (Uᵢ) | 1000V AC |
| Main Busbar Rated Current (Iₙ) | Up to 4000A |
| Rated Short-Time Withstand Current (I꜀w) | 50kA / 65kA (1s) |
| Ingress Protection Rating | IP42 / IP54 (Custom enclosure options) |
| Enclosure Material & Thickness | 2.0mm Cold-Rolled Steel / Electro-Galvanized Sheet |
| Modular Frame Grid | 25mm Pitch Grid Structure |
| Form of Internal Separation | Form 3b / Form 4a (IEC 61439-2) |
| Compliance Standards | IEC 61439-1/2, GB/T 7251.12, CE Certified |
Commercial mall environments present specific electrical engineering constraints. The modular assembly design directly addresses these challenges:

With over 15 years of technical manufacturing experience in low-voltage switchgear and custom power assemblies, our production facilities follow strict quality verification protocols:
We integrate multi-channel digital energy meters supporting Modbus-RTU, BACnet, or Ethernet communications. This enables real-time sub-metering for individual tenant billing directly integrated into the mall's facility management platform.
The structural frame utilizes a standardized 25mm hole pattern. Extra functional compartments can be pre-configured with blind covers, allowing maintenance engineers to install additional withdrawable units or branch circuit breakers without modifying the main enclosure or busbar system.
Form 3b or Form 4a internal separation is recommended. These configurations isolate the busbars, functional units, and external terminals into individual compartments, preventing accidental contact or arc fault propagation to adjacent circuits during maintenance.
Yes. The modular compartments can house dual-power automatic transfer switching systems (ATS) linked directly to backup diesel generators or secondary grid feeds, ensuring automatic power restoration to essential emergency lighting and life safety equipment.
|