| Sign In | Join Free | My benadorassociates.com |
|
| Company Info. |
| Shenzhen Ruifujie Technology Co., Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |

| Parameter | Value |
|---|---|
| Model | SP4LF1000, SP4LF100E |
| Rated Power | 10 HP / 7.5 kW |
| Exhaust Volume (50/60 Hz) | 49 / 58.8 m³/hr |
| Cylinders | 4 |
| Weight | 144 kg |
| Oil Charge | 2.6 L |
| Energy Regulation | 100%, 50% |
| Standard Motor | 400V/3/50Hz, 460V/3/60Hz PW |
| Starting Current (PW/DOL) | 71 / 110 A |
| Max Operating Current | 24 A |
| Oil Lubrication Method | Pressure lubrication (with oil pump) |

A1: To determine exact suitability, please provide your required cooling capacity, operating evaporation and condensation temperatures, power supply standards, and target application details.
A2: System lines must be thoroughly pressure-tested, evacuated, and checked for cleanliness, while ensuring the crankcase heater has warmed the lubrication oil sufficiently before starting the motor.
A3: The built-in INT69VS protection module monitors winding temperature and power conditions, automatically triggering a safety shutdown if overheating or phase irregularities occur.
A4: Technicians should periodically verify oil level and clarity through the sight glass, inspect suction filter cleanliness, and log operating currents to detect system abnormalities early.
|