| Sign In | Join Free | My benadorassociates.com |
|
| Categories | Rack Fire Suppression Unit |
|---|---|
| Brand Name: | XINGJIN |
| Model Number: | 40L/70L/100L/120L/180L/245L |
| Certification: | GSG\TUV\GB6653-2008 |
| Place of Origin: | Guangzhou,China |
| MOQ: | 5 set |
| Price: | Pricing based on quantity |
| Payment Terms: | T/T, L/C |
| Supply Ability: | 30000 sets per month |
| Delivery Time: | 15-20days |
| Packaging Details: | Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper |
| Nominal volume: | 40L/70L/100L/120L/180L/245L |
| Actual volume: | 40.5L/70.5L/100.5L/120.5L/180.5L/245.5L |
| Internal diameter: | 267/300/325/350/400mm |
| Total length: | 757±15/898±10/1213±10/1414±10mm... |
| Filling medium: | FM200+nitrogen |
| Designed thickness of cylinder: | 5.4 mm |
| Company Info. |
| Guangzhou Xingjin Fire Equipment Co.,Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |
FM200 Pipe Network Gas Cylinder
Overall system introduction:
The HFC-227ea automatic fire extinguishing system consists of a
fire extinguishing agent bottle group, a bracket, a drive gas
bottle group, a container valve, a liquid check valve, a gas check
valve, a drive device, a gas transmission control pipeline, a
manifold, a selection valve, a tee, a reducing tee, an elbow, a
reducing elbow, a flange, a safety valve, a signal feedback device,
a pipe network, a nozzle, a reagent, a fire detector, a gas fire
extinguishing controller, an audible and visual alarm, an alarm, a
deflation indicator light, an emergency start/stop button, etc.
Fire Extinguishing Agent Cylinder Set
1) Purpose: Used to store HFC-227ea fire extinguishing agent, with functions
such as sealing, releasing, filling, overpressure relief, and
pressure display.
2) Structure: Consists of a container valve, siphon tube, and storage container.
The storage container is a refillable, red epoxy-painted, welded
steel container. The container valve consists of a valve body,
actuating device, a piston, a pressure indicator, and a pressure
relief device. After connecting to the siphon tube, it is installed
on the mouth of the storage container. The container valve can be
opened pneumatically or manually to release the fire extinguishing
agent.
3) Main Technical Parameters:
| Model specifications | Storage pressure | Volume (L) | Container Valve Model | Nominal diameter (mm) | Equivalent length (m) | Outer diameter (mm) | H | Net weight (Kg) |
| QMP70/5.6 | 5.6MPa | 70 | QRF32/8 | 32 | 6 | 267 | 1560 | 86 |
| QMP90/5.6 | 5.6MPa | 90 | QRF32/8 | 32 | 6 | 325 | 1440 | 130 |
| QMP120/5.6 | 5.6MPa | 120 | QRF32/8 | 32 | 6 | 325 | 1600 | 139 |
4) Installation and Instructions:
1) The installation location should comply with the requirements of
the design documents and be arranged in the order of the cylinder
group numbers. The height difference should not exceed 20mm, and
the distance between the operating surface and the wall or between
operating surfaces should not be less than 1.0m.
2) In an emergency, remove the safety pin on the actuator, engage
the handle one by one, and activate the cam lever to open all the
container valves to release the fire extinguishing agent.
5) Maintenance Instructions:
Perform a monthly visual inspection to ensure there is no
deformation or mechanical damage from impact, no surface rust, an
intact protective coating, and the safety pin and seal are intact
before continuing to use.
6) Note:
The safety pin on the container valve is used to lock the cam
lever. Pulling out the safety pin before disengaging the cam lever
is necessary only for manual actuation of the container valve.
Locking the cam lever does not affect the nitrogen actuation of the
container valve.
Detailed parameters:
| Specification | inner diameter | Bottle thread | Valve outlet aperture | Bottle height | Bottle + container valve height | Total height of bottle + container valve + solenoid valve |
| 40L*5.6MPa | ø300 | M80*2 | 50 | 757±15 | 897±15 | 1057±15 |
| 70L*5.6MPa | ø350 | M80*2 | 50 | 898±10 | 1038±10 | 1198±10 |
| 100L*5.6MPa | ø350 | M80*2 | 50 | 1213±10 | 1353±10 | 1513±10 |
| 120L*5.6MPa | ø350 | M80*2 | 50 | 1414±10 | 1554±10 | 1714±10 |
| 150L*5.6MPa | ø400 | M80*2 | 50 | 1395±10 | 1535±10 | 1695±10 |
| 180L*5.6MPa | ø400 | M80*2 | 50 | 1630±10 | 1770±10 | 1930±10 |
| 70L*17.2 | ø267 | PZ56 | 32 | 1499±10 | 1679±10 | / |
| 90L*17.2 | ø325 | PZ56 | 32 | 1420±10 | 1600±10 | / |
| 120L*17.2 | ø325 | PZ56 | 32 | 1835±10 | 2015±10 | / |

|