| Sign In | Join Free | My benadorassociates.com |
|
| Categories | Foam Fire Suppression System |
|---|---|
| Brand Name: | XINGJIN |
| Model Number: | XJ-QEO-006 |
| Certification: | CCC,CAC,ROHS |
| Place of Origin: | Guangzhou,China |
| MOQ: | 5 set |
| Price: | Pricing based on quantity |
| Payment Terms: | T/T, L/C |
| Supply Ability: | 30000set/month |
| Delivery Time: | 15-20days |
| Packaging Details: | Wooden Box Or Plywood Outer Box With Bubble Bag Or Paper |
| Drug Output Pressure: | 0~3.6 MPa |
| Filling Pressure Alarm: | 0~10 MPa (Adjustable, The Alarm Light Will Turn on |
| Filling Accuracy: | ±0.5% |
| Power Requirements: | AC 220V,50Hz |
| External Connection Thread: | Threads for Reagent Inlet and Outlet and Nitrogen |
| Trademark: | Xingjin |
| Production Capacity: | 30000 Sets Per Month |
| Nitrogen Decompression Range: | 0~10 MPa Adjustable (Commonly Used: 4.2 MPa, 5.6 M |
| Vacuum Degree: | ≤ -0.09 MPa |
| Filling Density: | ≤ 1420 Kg/M³ |
| Ambient Temperature: | 0~50℃ |
| Equipment Size: | 720×800×1280 mm (Excluding Runner) |
| Transport Package: | Wooden Box or Plywood Outer Box with Bubble Bag or |
| Origin: | Guangzhou, China |
| Company Info. |
| Guangzhou Xingjin Fire Equipment Co.,Ltd. |
| Verified Supplier |
| View Contact Details |
| Product List |
Product Description:
The perfluorohexanone fire extinguishing agent filling equipment is
a professional device that combines efficiency, safety, and
precision, suitable for the maintenance and installation of
perfluorohexanone fire extinguishing systems. Equipped with
nitrogen pressure reduction, a filling pressure alarm, a vacuum
system, and a reserved interface for weight alarm nodes, the
equipment supports a variety of gas cylinder sizes, ensuring
airtightness and accuracy during the fire extinguishing agent
filling process.
Equipment valve body function:
F1 Pressure Reducing Valve | Control the pressure of nitrogen when it enters the system to
ensure a stable and safe filling process. |
F2 pressure relief valve | Release excess pressure in an emergency to protect equipment and
gas cylinders from high pressure damage. |
F3 Chemical Storage Valve | Control the flow of fire extinguishing agent from the agent storage
tank to the filling cylinder. |
F4 Nitrogen Storage Valve | Control the nitrogen gas from the storage tank into the equipment
pipeline to provide pressure for filling the fire extinguishing
agent. |
F5 gas cylinder valve | Used to connect fire extinguishing agent cylinders and control the
opening or closing of the cylinder fluid channel. |
F6 Vacuum Valve | Used to open or close the extraction of air from the gas cylinder
to reduce the pressure inside the cylinder and ensure the purity of
the fire extinguishing agent. |
F7 valve | Control the flow of perfluorohexanone into the gas cylinder |
F8 valve | Controlled access to gas cylinders |
F9 valve | Control the passage of nitrogen into the gas cylinder and provide
pressure for the gas cylinder. |
Heptafluoropropane filling operation:
Volume | 8L-30L | 40L | 70L | 90L | 100L | 120L | 150L | 180L |
Minimum vacuum time | 30s | 40S | 50S | 56S | 60S | 65S | 78S | 93S |