| Brand Name: | Hima |
| Model Number: | F6214 |
| Place of Origin: | Germany |
| MOQ: | 1 |
| Price: | 66USD |
| Payment Terms: | T/T |
| Supply Ability: | in stock |
| Delivery Time: | 2-3 work days |
| Packaging Details: | Brand new and original |
| voltage inputs: | 0...1/5/10 V |
| current inputs: | 0...20 mA, with safety isolation |
| resolution: | 12 bits |
| Electric strength: | 250 V against GND |
| Space requirement: | 4 TE |
| Operating data( 5 V DC): | 150 mA |
| Operating data(24 V DC): | 250 mA |
| Packaging: | Original New Packaging |
| Company Info. |
| AMIKON LIMITED |
| Verified Supplier |
| View Contact Details |
| Product List |

| Item | Specification |
|---|---|
| Product Model | F6214 |
| Product Type | Analog Input Module |
| Manufacturer | HIMA |
| Country of Origin | Germany |
| Place of Shipment | Xiamen, China |
| Estimated Shipping Size | 2.5 × 12.7 × 20.3 cm |
| Weight | 0.1 kg |
| Input Voltage | 0 … 1.06 V |
| Digital Values | 0 mV = 0, 1 V = 3840 |
| Wait After Test | 100 ms |
| Shunt | 50 Ω; 0.05%; 0.125 W |
| Current Input | T < 10 ppm/K; Part No. 00 0710500 |
| Input Resistance | 1 MΩ |
| Input Filter Time Constant (Approx.) | 10 ms |
| Transmitter Supply | 20 … 25 V, 0 … 22 mA |
| Short Circuit Current | 25 mA |
| Operating Error | 0.3% at 0 … +60 °C |

Ensure high availability and signal integrity by connecting passive transmitters redundantly to the F6214 HIMA Analog Input Module.
Implementation Steps
Step 1 – Transmitter Selection
Use passive (loop-powered) transmitters compatible with voltage
input ranges supported by the F6214. Verify that transmitter output
characteristics match the module’s input specification.
Step 2 – Parallel Redundant Wiring
Connect two passive transmitters in parallel to the analog input
channel. Each transmitter is wired through an individual precision
shunt resistor, ensuring independent signal paths while maintaining
redundancy.
Step 3 – Input Conditioning
Utilize the module’s internal 50 Ω precision shunt and high input
resistance (1 MΩ) to convert the transmitter current signal into a
voltage signal without introducing significant loading effects.
Step 4 – Power Supply Integration
Provide transmitter supply voltage via the module’s integrated
transmitter supply (20–25 V, 0–22 mA). Confirm short-circuit
protection limits (25 mA) to prevent damage during fault
conditions.
Step 5 – Validation and Monitoring
After wiring, allow the specified stabilization time (wait after
test: 100 ms) before signal evaluation. Verify correct digital
scaling (1 V = 3840 counts) and monitor for deviations indicating
transmitter or wiring faults.
Result
This redundant connection scheme increases system availability and
fault tolerance by allowing continued operation in the event of a
single transmitter or wiring failure, while maintaining measurement
accuracy within the specified operating error of 0.3% across the
operating temperature range.

Location: Port of Xiamen, China
Condition: Factory New (Original Box)
Availability: Immediate Stock
Carriers: FedEx / DHL / TNT / UPS
Packing: Shock-resistant Foam + Reinforced Carton
Warranty: 1 Year (12 Months)
Updates: Tracking, Weight & Dims provided post-shipment
Terms: 100% T/T before shipping
Miya Zheng
Amikon Sales Manager
sales@amikon.cn | +86 180 2077 6792

| HIMA | HIMA | HIMA |
| HIMATRIX F60GEH01 F60 GEH 01 | F3330 | F7126 |
| HIMATRIX F3 DIO 8/8 01 | H7506 | F3322 |
| F8650X | F3237 | F2201 |
| HIMATRIX F3 DIO 20/8 02 | F3236 | F3417A |
| HIMATRIX F3DIO 8/8 01 F3 DIO 8/8 01 | F7105A | F4204 |
| HIMATRIX F2DO1602 F2 DO 16/02 | Z7116 | F1101 |
| F6705 | HIMATRIX F2 DO8 01 | F3113A |
| F7131 | F3221 | F3423 |
| F6217 | F8641 | F7130 |
| F7130A | K9203 | Z7126 |
|